Backflow assembly test: 8360 Turkey Hill Way

Approved

Filed Sep 26, 2024 by Emerson Marsh, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 26, 2024
Assembly type
RP
Serial number
K754045
Size
1
Test gauge serial
G-6390
Gauge calibration date
Jan 25, 2024
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-35-01118
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.