Back to the backflow review queue

Backflow assembly test: 9585 Turkey Hill Ln

Approved

Filed Oct 17, 2026 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 17, 2026
Assembly type
DC
Serial number
K883990
Size
3/4
Test gauge serial
G-4918
Gauge calibration date
Feb 4, 2026
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-52-01196
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9585 Turkey Hill Ln
Owner: Logan Ellery
Parcel 009-52-01196