Backflow assembly test: Blue Heron Car Wash

Approved

Filed Sep 13, 2026 by Avery Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Sep 13, 2026
Assembly type
RP
Serial number
Z838551
Size
2
Test gauge serial
G-6318
Gauge calibration date
Mar 21, 2026
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.7 psid
Relief valve opened at
4.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 009-50-01169
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1520 Spring Branch Ct
Owner: Calloway Holdings LLC
Parcel 009-50-01169