Back to the backflow review queue

Backflow assembly test: 3000 Quarry Rd

Approved

Filed Sep 20, 2025 by Emerson Marsh, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 20, 2025
Assembly type
RP
Serial number
Z155652
Size
3/4
Test gauge serial
G-1492
Gauge calibration date
Jul 27, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-49-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3000 Quarry Rd
Owner: Alex Fairley
Parcel 009-49-01114