Backflow assembly test: 5086 Sycamore Trl

Approved

Filed Oct 23, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 23, 2025
Assembly type
RP
Serial number
K579785
Size
3/4
Test gauge serial
G-7379
Gauge calibration date
Oct 4, 2024
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-42-01287
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5086 Sycamore Trl
Owner: Sam Marsh
Parcel 009-42-01287