Backflow assembly test: Station Pizza
ApprovedFiled Mar 31, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 31, 2025
- Assembly type
- RP
- Serial number
- W518736
- Size
- 2
- Test gauge serial
- G-5294
- Gauge calibration date
- Jan 4, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Marsh, current on the service date
- All required fields present
- Address matches parcel 009-65-01327
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.