Back to the backflow review queue

Backflow assembly test: 3610 Meadow Lark Ln

Approved

Filed Sep 15, 2026 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Sep 15, 2026
Assembly type
DC
Serial number
W200043
Size
3/4
Test gauge serial
G-4057
Gauge calibration date
Dec 17, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-93-01082
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3610 Meadow Lark Ln
Owner: Logan Lindqvist
Parcel 013-93-01082