Back to the backflow review queue

Backflow assembly test: 1986 Laurel Way

Approved

Filed Feb 24, 2026 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Feb 24, 2026
Assembly type
DC
Serial number
A923946
Size
3/4
Test gauge serial
G-1123
Gauge calibration date
Jun 10, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-10-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1986 Laurel Way
Owner: Logan Fairley
Parcel 013-10-01320