Backflow assembly test: 3415 Meadow Lark Dr
ApprovedFiled Dec 26, 2024 by Parker Ashby, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 26, 2024
- Assembly type
- PVB
- Serial number
- W271249
- Size
- 1
- Test gauge serial
- G-3786
- Gauge calibration date
- Jul 6, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 013-12-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.