Back to the backflow review queue

Backflow assembly test: Station Bakery

Approved

Filed Dec 29, 2023 by Casey Calloway, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 29, 2023
Assembly type
DC
Serial number
A689124
Size
4
Test gauge serial
G-6042
Gauge calibration date
Oct 19, 2023
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-31-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6812 Spring Branch Ln
Owner: Nguyen Holdings LLC
Parcel 013-31-01348