Backflow assembly test: 8459 Orchard Ln
ApprovedFiled Sep 29, 2024 by Blake Marsh, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 29, 2024
- Assembly type
- RP
- Serial number
- B940024
- Size
- 3/4
- Test gauge serial
- G-1719
- Gauge calibration date
- Jul 20, 2024
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Marsh, current on the service date
- All required fields present
- Address matches parcel 013-62-01206
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8459 Orchard Ln
Owner: Hayden Okafor
Parcel 013-62-01206