Back to the backflow review queue

Backflow assembly test: 8459 Orchard Ln

Approved

Filed Oct 29, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 29, 2025
Assembly type
RP
Serial number
B940024
Size
3/4
Test gauge serial
G-4503
Gauge calibration date
Feb 27, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-62-01206
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8459 Orchard Ln
Owner: Hayden Okafor
Parcel 013-62-01206