Backflow assembly test: 6246 Turkey Hill Ln
ApprovedFiled Nov 2, 2025 by Casey Benton, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 2, 2025
- Assembly type
- DC
- Serial number
- W786920
- Size
- 1
- Test gauge serial
- G-3954
- Gauge calibration date
- Mar 13, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Benton, current on the service date
- All required fields present
- Address matches parcel 013-57-01336
- Readings in range, no flags
- Result: passing. Next due date resets when approved.