Backflow assembly test: Blue Heron Bakery

Approved

Filed Dec 10, 2025 by Morgan Vance, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Dec 10, 2025
Assembly type
RP
Serial number
K550275
Size
2
Test gauge serial
G-9285
Gauge calibration date
Oct 26, 2024
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Vance, current on the service date
  • All required fields present
  • Address matches parcel 013-45-01080
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5838 Turkey Hill Trl
Owner: Ramirez Holdings LLC
Parcel 013-45-01080