Back to the backflow review queue

Backflow assembly test: 9639 Quarry Trl

Approved

Filed Dec 17, 2025 by Blake Marsh, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 17, 2025
Assembly type
RP
Serial number
K147376
Size
1
Test gauge serial
G-6303
Gauge calibration date
Jul 6, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-70-01137
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9639 Quarry Trl
Owner: Taylor Danner
Parcel 013-70-01137