Back to the backflow review queue

Backflow assembly test: Two Rivers Market

Approved

Filed Jul 14, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 14, 2025
Assembly type
RP
Serial number
W508526
Size
2
Test gauge serial
G-4620
Gauge calibration date
Jan 25, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-15-01102
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7767 Spring Branch Rd
Owner: Calloway Holdings LLC
Parcel 013-15-01102