Backflow assembly test: 6491 Turkey Hill Dr
ApprovedFiled Aug 23, 2025 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 23, 2025
- Assembly type
- RP
- Serial number
- B351032
- Size
- 3/4
- Test gauge serial
- G-6158
- Gauge calibration date
- Dec 18, 2024
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 013-72-01220
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.