Backflow assembly test: 6219 Turkey Hill Trl

Approved

Filed Dec 14, 2024 by Parker Ashby, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Dec 14, 2024
Assembly type
RP
Serial number
A576243
Size
3/4
Test gauge serial
G-5548
Gauge calibration date
Nov 14, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 013-93-01144
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.