Backflow assembly test: 6728 Orchard Ct
ApprovedFiled Sep 6, 2025 by Casey Benton, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 6, 2025
- Assembly type
- DC
- Serial number
- K938654
- Size
- 3/4
- Test gauge serial
- G-6634
- Gauge calibration date
- Mar 28, 2025
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Benton, current on the service date
- All required fields present
- Address matches parcel 013-17-01122
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.