Back to the backflow review queue

Backflow assembly test: 6728 Orchard Ct

Approved

Filed Aug 18, 2026 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 18, 2026
Assembly type
DC
Serial number
K938654
Size
3/4
Test gauge serial
G-6757
Gauge calibration date
May 4, 2026
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-17-01122
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6728 Orchard Ct
Owner: Cameron Whitcomb
Parcel 013-17-01122