Backflow assembly test: 3479 Turkey Hill Rd

Approved

Filed Mar 11, 2025 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 11, 2025
Assembly type
RP
Serial number
A335561
Size
3/4
Test gauge serial
G-2851
Gauge calibration date
Jun 2, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-69-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.