Back to the backflow review queue

Backflow assembly test: 7266 Pine Knoll Way

Approved

Filed Oct 23, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 23, 2025
Assembly type
PVB
Serial number
W823453
Size
1
Test gauge serial
G-5674
Gauge calibration date
Sep 2, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Calloway, current on the service date
  • All required fields present
  • Address matches parcel 013-62-01270
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7266 Pine Knoll Way
Owner: Morgan Vance
Parcel 013-62-01270