Backflow assembly test: Hilltop Elementary School

Approved

Filed May 7, 2026 by Jamie Whitcomb, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
May 7, 2026
Assembly type
RP
Serial number
W713570
Size
1
Test gauge serial
G-1308
Gauge calibration date
Sep 14, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 013-43-01064
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.