Back to the backflow review queue
Backflow assembly test: 6672 Laurel Ct
ApprovedFiled Aug 26, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 26, 2025
- Assembly type
- RP
- Serial number
- A527911
- Size
- 3/4
- Test gauge serial
- G-6004
- Gauge calibration date
- Jul 3, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-86-01068
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6672 Laurel Ct
Owner: Sam Fairley
Parcel 013-86-01068