Backflow assembly test: 7211 Ridgeview Dr
ApprovedFiled May 3, 2024 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 3, 2024
- Assembly type
- PVB
- Serial number
- Z759068
- Size
- 3/4
- Test gauge serial
- G-4412
- Gauge calibration date
- Jul 12, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-41-01326
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7211 Ridgeview Dr
Owner: Jordan Vance
Parcel 013-41-01326