Backflow assembly test: 328 Mill Creek Rd

Approved

Filed Jun 26, 2026 by Blake Marsh, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jun 26, 2026
Assembly type
RP
Serial number
B171159
Size
3/4
Test gauge serial
G-6318
Gauge calibration date
Mar 24, 2026
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
3.3 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-61-01056
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

328 Mill Creek Rd
Owner: Taylor Brandt
Parcel 013-61-01056