Back to the backflow review queue

Backflow assembly test: 8432 Sycamore Trl

Approved

Filed Oct 27, 2023 by Blake Marsh, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 27, 2023
Assembly type
PVB
Serial number
A428626
Size
1
Test gauge serial
G-7432
Gauge calibration date
Jul 7, 2023
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Marsh, current on the service date
  • All required fields present
  • Address matches parcel 013-64-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8432 Sycamore Trl
Owner: Logan Calloway
Parcel 013-64-01009