Approved

Filed Nov 26, 2024 by Casey Benton, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 26, 2024
Assembly type
PVB
Serial number
A428626
Size
1
Test gauge serial
G-7533
Gauge calibration date
May 23, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-64-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.