Backflow assembly test: Hilltop Apartments
ApprovedFiled Oct 9, 2025 by Casey Calloway, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 9, 2025
- Assembly type
- DC
- Serial number
- K157361
- Size
- 4
- Test gauge serial
- G-1058
- Gauge calibration date
- Aug 3, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Calloway, current on the service date
- All required fields present
- Address matches parcel 013-74-01150
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4188 Orchard Rd
Owner: Okafor Holdings LLC
Parcel 013-74-01150