Back to the backflow review queue

Backflow assembly test: 7553 Meadow Lark Dr

Approved

Filed Nov 16, 2026 by Avery Wexler, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 16, 2026
Assembly type
RP
Serial number
K623201
Size
1
Test gauge serial
G-4626
Gauge calibration date
Aug 10, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-66-01112
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7553 Meadow Lark Dr
Owner: Logan Whitcomb
Parcel 017-66-01112