Backflow assembly test: 8909 Quarry Ln

Approved

Filed May 22, 2026 by Logan Fairley, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 22, 2026
Assembly type
PVB
Serial number
K636768
Size
3/4
Test gauge serial
G-8864
Gauge calibration date
Sep 4, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 017-15-01033
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8909 Quarry Ln
Owner: Emerson Wexler
Parcel 017-15-01033