Back to the backflow review queue

Backflow assembly test: 5139 Turkey Hill Trl

Approved

Filed Aug 2, 2025 by Avery Wexler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 2, 2025
Assembly type
DC
Serial number
B304052
Size
3/4
Test gauge serial
G-6424
Gauge calibration date
Mar 24, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-17-01134
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5139 Turkey Hill Trl
Owner: Avery Whitcomb
Parcel 017-17-01134