Backflow assembly test: 3626 Quarry Trl
ApprovedFiled Sep 15, 2026 by Riley Marsh, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 15, 2026
- Assembly type
- DC
- Serial number
- A621126
- Size
- 1
- Test gauge serial
- G-7073
- Gauge calibration date
- May 12, 2026
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Marsh, current on the service date
- All required fields present
- Address matches parcel 017-32-01356
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3626 Quarry Trl
Owner: Casey Nguyen
Parcel 017-32-01356