Backflow assembly test: Station Brewing Co

Approved

Filed Jun 7, 2025 by Parker Stroud, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jun 7, 2025
Assembly type
DC
Serial number
A906881
Size
1
Test gauge serial
G-5972
Gauge calibration date
Oct 30, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-79-01173
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property