Backflow assembly test: 4052 Hickory Trl

Approved

Filed Jan 7, 2025 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jan 7, 2025
Assembly type
RP
Serial number
A531009
Size
1
Test gauge serial
G-2612
Gauge calibration date
Mar 15, 2024
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-89-01073
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4052 Hickory Trl
Owner: Reese Brandt
Parcel 017-89-01073