Backflow assembly test: 4915 Hickory Ct

Approved

Filed Aug 7, 2024 by Parker Stroud, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 7, 2024
Assembly type
RP
Serial number
W280999
Size
1
Test gauge serial
G-3836
Gauge calibration date
Aug 6, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-83-01094
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.