Back to the backflow review queue

Backflow assembly test: Main Street Bakery

Approved

Filed Apr 8, 2026 by Avery Wexler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Apr 8, 2026
Assembly type
RP
Serial number
A583455
Size
1 1/2
Test gauge serial
G-7177
Gauge calibration date
Feb 16, 2026
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 017-70-01233
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5570 Laurel Ct
Owner: Calloway Holdings LLC
Parcel 017-70-01233