Back to the backflow review queue
Backflow assembly test: 6681 Pine Knoll Rd
ApprovedFiled Jun 6, 2025 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 6, 2025
- Assembly type
- RP
- Serial number
- K127306
- Size
- 3/4
- Test gauge serial
- G-8029
- Gauge calibration date
- Feb 17, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Brandt, current on the service date
- All required fields present
- Address matches parcel 017-66-01201
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6681 Pine Knoll Rd
Owner: Taylor Harlow
Parcel 017-66-01201