Back to the backflow review queue

Backflow assembly test: 5245 Cedar Hollow Rd

Approved

Filed May 21, 2023 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 21, 2023
Assembly type
RP
Serial number
K707525
Size
1
Test gauge serial
G-2549
Gauge calibration date
Jul 26, 2022
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-36-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5245 Cedar Hollow Rd
Owner: Alex Ellery
Parcel 017-36-01050