Backflow assembly test: Riverside Grill

Approved

Filed Sep 4, 2024 by Avery Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 4, 2024
Assembly type
DC
Serial number
B300523
Size
1 1/2
Test gauge serial
G-7218
Gauge calibration date
Dec 25, 2023
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-29-01042
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6758 Cedar Hollow Ln
Owner: Brandt Holdings LLC
Parcel 017-29-01042