Backflow assembly test: Riverside Grill
ApprovedFiled Aug 20, 2025 by Riley Brandt, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 20, 2025
- Assembly type
- DC
- Serial number
- B300523
- Size
- 1 1/2
- Test gauge serial
- G-8998
- Gauge calibration date
- Mar 30, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Brandt, current on the service date
- All required fields present
- Address matches parcel 017-29-01042
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.