Backflow assembly test: Two Rivers Self Storage
ApprovedFiled May 6, 2025 by Parker Stroud, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- May 6, 2025
- Assembly type
- RP
- Serial number
- W600665
- Size
- 2
- Test gauge serial
- G-7325
- Gauge calibration date
- Oct 31, 2024
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Stroud, current on the service date
- All required fields present
- Address matches parcel 017-76-01185
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3889 Laurel Ct
Owner: Danner Holdings LLC
Parcel 017-76-01185