Backflow assembly test: Two Rivers Self Storage

Approved

Filed Jun 3, 2026 by Avery Ashby, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 3, 2026
Assembly type
RP
Serial number
W600665
Size
2
Test gauge serial
G-8322
Gauge calibration date
Apr 7, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-76-01185
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3889 Laurel Ct
Owner: Danner Holdings LLC
Parcel 017-76-01185