Back to the backflow review queue

Backflow assembly test: Two Rivers Market

Filed Nov 21, 2026 by Logan Fairley, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
W620499
Size
1
Test gauge serial
G-6741
Gauge calibration date
Jun 18, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 017-35-01346
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7946 Spring Branch Ct
Owner: Kessler Holdings LLC
Parcel 017-35-01346