Backflow assembly test: 2057 Ridgeview Trl

Approved

Filed Jun 22, 2026 by Logan Fairley, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 22, 2026
Assembly type
RP
Serial number
Z900456
Size
1
Test gauge serial
G-3433
Gauge calibration date
Feb 23, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Relief valve opened at
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 017-26-01106
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2057 Ridgeview Trl
Owner: Parker Ashby
Parcel 017-26-01106