Back to the backflow review queue

Backflow assembly test: 8269 Laurel Way

Approved

Filed Nov 13, 2024 by Avery Ashby, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 13, 2024
Assembly type
RP
Serial number
K694653
Size
3/4
Test gauge serial
G-2107
Gauge calibration date
Feb 11, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ashby, current on the service date
  • All required fields present
  • Address matches parcel 017-31-01036
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8269 Laurel Way
Owner: Alex Danner
Parcel 017-31-01036