Back to the backflow review queue

Backflow assembly test: 5804 Laurel Trl

Approved

Filed Sep 6, 2026 by Riley Brandt, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 6, 2026
Assembly type
DC
Serial number
K396066
Size
3/4
Test gauge serial
G-2863
Gauge calibration date
Apr 28, 2026
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Brandt, current on the service date
  • All required fields present
  • Address matches parcel 017-15-01261
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5804 Laurel Trl
Owner: Blake Harlow
Parcel 017-15-01261