Backflow assembly test: 1196 Old Church Way
ApprovedFiled Jun 16, 2026 by Avery Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 16, 2026
- Assembly type
- DC
- Serial number
- K865528
- Size
- 1
- Test gauge serial
- G-3608
- Gauge calibration date
- Nov 28, 2025
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ashby, current on the service date
- All required fields present
- Address matches parcel 017-95-01021
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1196 Old Church Way
Owner: Hayden Nguyen
Parcel 017-95-01021