Report
- Date of service
- Mar 9, 2024
- Assembly type
- DC
- Serial number
- A316845
- Size
- 3/4
- Test gauge serial
- G-3788
- Gauge calibration date
- Sep 23, 2023
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Marsh, current on the service date
- All required fields present
- Address matches parcel 017-59-01258
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.