Back to the backflow review queue

Backflow assembly test: Corner Pizza

Approved

Filed Feb 17, 2026 by Parker Stroud, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 17, 2026
Assembly type
RP
Serial number
A721845
Size
2
Test gauge serial
G-9263
Gauge calibration date
Dec 9, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Stroud, current on the service date
  • All required fields present
  • Address matches parcel 017-71-01076
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2888 Laurel Ln
Owner: Benton Holdings LLC
Parcel 017-71-01076